I have a generator that isn't producing power. K1 relay is fine, K15 relay works, AC voltage from Magnetic pickup to Crank Disconnect Switch is within range (2.4 VAC). What I am trying to find is the proper voltage to F+ and F- terminals on the voltage regulator. I have 24 volts coming in to R14 resistor, but only 8 leaving. I am wondering if this is sufficient voltage to for the field flash circuit to energize.
↧